Design the concrete mix according to the following conditions:
Design Environment
Building frame
Required design strength = 27.6 MPa
Minimum dimension = 150 mm
Minimum space between rebar = 40 mm
Minimum cover over rebar = 40 mm
Maximum slump is required
Statistical data indicate a standard deviation of compressive strength of 2.1 MPa is
expected (more than 30 samples).
Only air entrainer is allowed.
Available Materials
Air entrainer: Manufacture specification 6.3 ml/1% air/100 kg cement. (Use maximum
or +2% air content)
Coarse aggregate: 19 mm nominal maximum size, river gravel (rounded)
Bulk oven-dry specific gravity = 2.55, Absorption = 0.3%
Oven-dry rodded density = 1761 kg/m³
Moisture content = 2%
Fine aggregate: Natural Sand
Bulk oven-dry specific gravity = 2.6
OR BUILDING SLUMP IS 25-100
FOR 19MM AGGREGATE SIZE
WATER REQUIRED IS 168KG/CUM
FOR STRENGTH OF CONCRETE =27.6
CORRESPONDING WATER CEMENT RATIO IS 0.48
WATER=168
Cement required =168/(0.4)=247kg/cum
for fineness of =2.47
and for aggregates size=19mm
Aggregate required =0.65 cum
density of AGGREGATE =1761
wt of aggregates =0.65"\\times" ×1761=1144kg/cum
wt of cement =247
wt of water =168
wt of aggregates =1144
density of water =1000kg/cum
vol of water =0.168 cum
density of cement =1400kg/cum
vol of cement =0.176
vol of AGGREGATE =0.65
vol of water=0.168
vol of cement =0.176
due to moisture and absorption
reduce volume
volume =0.63
vol of water =0.15
vol of cement =0.16
vol of fine =1-0.63-0.15-0.16=0.06 cum
vol of agg=0.63
vol of fine =0.06
vol of water =0.15
vol of cement =0.16
wt of aggregates =0.63×1761
=1109kg
wt of water =150 kg
wt of cement =210 kg
wt of fine =2.659×1000×0.06=159.6 kg
These are required for 1 cum of concrete